Project North
|
North Carolina Site, Combination Tier II and Tier III Data Center totaling 52,000 square feet. Completion last quarter 2007. Mission Critical Environment.
Facility integration services include direct integration into Trane chillers, Bacharach refrigerant monitoring system, Caterpillar generators via EMCP controllers, Liebert SiteLink integration to UPS and PDU's, and a LON-based mechanical DDC system. Modbus is as much a part of our business in this project as any other field bus.
- Hydronic cooling of technical area.
- Direct LON Integration into Trane Chillers, Bacharach refrigerant monitor, ABB VFD
- Modbus integration into UPS, PDU's, Eaton Switch gear, Caterpillar generators, CRAC units
- Discreet monitoring and control of Hydrogen detection system
- TVSS for TVSS failure alarms
- Connection of battery chargers for charger fail, low battery voltage, and high battery voltage
- Connection of transfer switch to monitor normal power and auxiliary power